Conventions in This Document

MSG is a message from the power supply to the controller.

CMD is a message from the transceiver to the power supply.


Hardware

The Flatpack2's CAN bus runs at 125kbps with 29-bit extended IDs, referenced to the PSU's negative rail.

If your breakout PCB exposes GNDD (the third small contact next to CANH and CANL), connect your transceiver GND to GNDD.
If GNDD is not available, connect your transceiver GND to the supply's VOUT-.

Failure to tie your transceiver's GND to GNDD or VOUT- will probably brutally murder your transceiver.

If possible, use a CAN transceiver which can tolerate in excess of 55V bus fault voltage such as the MAX3305x and its 5V siblings; this makes transceiver damage less likely in the event of it being miswired.

I am using a MAX3051 in my application but the drop-in replacement MAX33053 would be a better idea.


Notes

I can't confirm whether any of this protocol data is correct for models other than the Flatpack2 HE 48V/2000W and Flatpack2 HE 48V/3000W. That said, anecdotal evidence from posters on various forums suggests the Flatpack S models are command-compatible and will work as well.

I'd expect it to work with any black-fronted Flatpack2 (HE/SHE) or Flatpack S model, but am unable to confirm.


ID-less Messages

These messages do not contain a PSU ID in their identity field, and are primarily used to discover PSUs and assign addresses to them.

CMD Log in, 0x050048XX

Log in to a power supply and assign it a CAN ID. Serial number payload chooses which supply to target.

PSU ID is assigned by setting XX to (ID * 4), e.g. sending message ID 0x05004804 assigns PSU ID of 0x01 for future commands.

Allowable ID range is 0x01 to 0x3F, or an XX of 0x04 through 0xFC, and the power supply will log out if no login packet is received for (64 * 0.2) seconds.

Byte 0 1 2 3 4 5 6 7
Value Power supply's serial number 0x00 0x00

MSG CAN hello packet, 0x0500XXXX

A supply that is not logged in will send this packet every two seconds or so.

XXXX is the last two bytes of the PSU's serial number.

Byte 0 1 2 3 4 5 6 7
Value 0x1B Power supply's serial number 0x00

PSU-specific Messages

These messages contain the PSU's assigned ID number, XX, in their message ID.

Sending messages to ID 0xFF will command all power supplies on the bus - I think this only works for the 'Set voltage and current limits' command, untested.

At the moment I actually can't get single-supply commands to work at all, so that's... odd.

MSG Status, 0x05XX40YY

Once a power supply is logged in and has an address assigned, it will send these packets every 0.2 seconds exactly 64 times.

Transmit count is reset to 64 whenever a login is received; logging in every 10 seconds (or 5 to be safe) should be adequate to stay logged in.

Current is in deciAmps (A * 0.1), voltages are all in centiVolts (V * 0.01), all in little-endian byte order.

Value of YY Power supply state
0x04 Normal (Constant Voltage)
0x08 Normal (Constant Current)
0x0C Alarm
0x10 Walk in (voltage ramping up)
Byte 0 1 2 3 4 5 6 7
Value Intake Temp Iout Vout Vin Exhaust Temp
Unit °C dA (A * 0.1) cV (V * 0.01) Vrms (AC) °C

MSG Login request / start-up notification, 0x05XX4400

Sent by a logged-out power supply every ten seconds or so. Similar to the CAN hello packet, but uses supply's pre-set ID.

Byte 0 1 2 3 4 5 6 7
Value Power supply's serial number 0x00 0x00

CMD Set voltage and current limits, 0x05xx4004

Sent to the power supply to immediately set output voltage and current limits.
If the supply logs out, these settings will be lost - default voltage will apply, and current limit will be set to factory maximum.

Max current is the point at which the supply will switch from CV to CC modes.
Please note that the supply will not go below its minimum output voltage in CC mode!

Desired voltage is the output voltage setpoint.

Measured voltage is for calibration/feedback; if you do not have a feedback voltage source, it should be equal to desired voltage.

OVP voltage is the voltage at which over-voltage protection will enable & cause the supply to shut down. Set this to your supply's maximum rated output voltage.

Max current is in deciAmps (A * 0.1), voltages are all in centiVolts (V * 0.01), all in little-endian byte order.

Byte 0 1 2 3 4 5 6 7
Value Max Current Measured Voltage Desired Voltage OVP Voltage
Unit dA (A * 0.1) cV (V * 0.01) cV (V * 0.01) cV (V * 0.01)

CMD Set default voltage, 0x05XX9C00

Sent to the power supply to set its default voltage. Does not take effect until the supply is logged out. If the supply is logged in when the command is sent, the voltage is set when the log in times out. If it is not logged in, the voltage will be set when the supply logs in then times out.

Voltage is stored in the same format as the status message - centivolts (V * 0.01) in little-endian byte order.

Byte 0 1 2 3 4
Value 0x29 0x15 0x00 New voltage

CMD Alert request, 0x05XXBFFC

Requests current alerts (warnings/alarms) from targeted power supply.

Send this after receiving a status message with a last byte of 0x08 or 0x0C to return current alert flags.

2nd byte of payload dictates whether query is for warning or critical alerts, and can be copied from the last byte of the status message.

Byte 0 1 2
Value 0x08 0x04 (warnings), 0x08 (alarms) 0x00

MSG Alert information, 0x05XXBFFC

Response to CMD 0x05XXBFFC, containing requested alert information.

2nd byte indicates whether flag bits are warning or critical, and is equal to 2nd byte of CMD packet.

Byte 0 1 2 3 4 5 6
Value 0x0E 0x04 (Warning) / 0x08 (Critical) 0x00 Alert flag byte 1 Alert flag byte 2 0x00 0x00

Alert flag bit mapping:

Bit Alert flag byte 1 Alert flag byte 2
0 OVS Lock Out Internal Voltage
1 Mod Fail Primary Module Fail
2 Mod Fail Secondary Mod Fail Secondary
3 High Mains Fan 1 Speed Low
4 Low Mains Fan 2 Speed Low
5 High Temp Sub Mod1 Fail
6 Low Temp Fan 3 Speed Low
7 Current Limit Inner Volt